کنتور هوشمند اشنایدر الکتریک

کنتور هوشمند اشنایدر الکتریک

  • Product Or Component Type: energy and power quality meter
  • Range: PowerLogic
  • Provided Equipment: remote display || remote display adapter || mounting instructions || Mounting Hardware
  • Device Application: power monitoring || WAGES metering || Net metering || medium voltage || high voltage
  • Device Short Name: ION92040
  • Metering Type: demand current I1, I2, I3, I4, I5 || peak demand currents || demand power P, Q, S || peak demand power PM, QM, SM || calculated active and reactive energy (+/- W.h, +/- VAR.h)

Complementary

  • Network Frequency: 50 Hz || 60 Hz
  • [Us] Rated Supply Voltage: 90...480 V AC 45...66 Hz +/- 10 % || 90...120 V AC 400 Hz +/- 10 % || 110...480 V DC +/- 15 %
  • Communication Port Support: 2 RS485 removable screw terminal block
  • Power Quality Analysis: EN 50160 compliance checking || IEEE 519 harmonic limit || IEC 61000-4-30 class A compliance reporting || IEEE 519 compliance reporting || waveform capture || total demand distortion || total harmonic distortion || up to the 63rd harmonic || up to the 127th harmonic with software || disturbance direction detection || dip, swell and transient || half cycle data acquisition || transient detection (20 µs)
  • Height: 160 mm
  • Measurement Voltage: 57-400 V AC 42...69 Hz between phase and neutral || 100-690 V AC 42...69 Hz between phases
  • Sampling Rate: 1024 samples/cycle
  • Memory Capacity: 2 GB
  • Number Of Outputs: 4 digital || 2 form C relay output
  • Type Of Measurement: voltage sags and swells || current sags and swells || voltage || current || frequency || active and reactive power total || apparent power total || active and reactive power per phase || apparent power per phase || power factor total || power factor per phase || active and reactive energy || apparent energy || harmonic distorsion (I THD & U THD)
  • Communication Port Protocol: Modbus RTU 2400...115200 bps - 2-wire || ION 2400...115200 bps - 2-wire || DNP3 2400...115200 bps - 2-wire || Modbus TCP 10/100 Mbit/s || ION TCP 10/100 Mbit/s || DNP3 TCP 10/100 Mbit/s || IEC 61850 || Ethernet Modbus TCP/IP daisy chain 10/100 Mbit/s || DHCP || DNS || DLMS
  • Frequency Measurement Range: 20-450 Hz
  • Communication Service: compliant reports || power quality summary || energy report || EcoStruxure Power Events Analysis || SMTP e-mail notification || SNMP
  • Ride-Through Time: 100 ms 6 cycles at 60 Hz 120 V AC typical || 400 ms 24 cycles at 60 Hz 240 V AC typical || 1200 ms 72 cycles at 60 Hz 480 V AC typical
  • Port Ethernet: 10/100BASE-TX 2 RJ45
  • Display Resolution: 800 x 480 pixels
  • Power Consumption In Va: 38 VA 480 V AC
  • Net Weight: 1.5 kg
  • Tamperproof Of Settings: protected by sealable cover
  • Measurement Current: 0.01-20 A
  • Electrical Insulation Class: class III EN/IEC 62052-11
  • Number Of Inputs: 8 digital 30 V AC/60 V DC
  • Time Synchronisation Protocol: GPS || IRIG-B || NTP || SNTP || PTP
  • Measurement Accuracy: voltage +/- 0.1 % || current +/- 0.1 %
  • Ethernet Service: DHCP client || Device Profile Web Services (DPWS) || Rapid Scanning Tree Protocol (RSTP) || FTP/HTTP/HTTPS
  • Mounting Support: DIN rail meter device || door cut-out remote display
  • Communication Gateway: Ethernet/serial
  • Poles Description: 3P + N + E
  • Data Recording: time stamping || min/max of instantaneous values || user-definable data logs || continuous logging or snapshot || trending/forecasting || event logs || alarm logs || configuration change || power outage || user login/logout || data logs || GPS synchronisation || sequence of event recording
  • Line Rated Current: 1 A || 5 A
  • Cybersecurity: Syslog protocol support || robust security logs || port hardening || enable/disable communication ports || hardware metrology lock
  • Isolation Voltage: III400-690 V conforming to EN 61010-1:ed. 3 || III347-600 V conforming to UL 61010-1:ed. 3 || III347-600 V conforming to CSA C22.2 No 61010-1:ed. 3
  • Analogue Input Type: voltage 5 MOhm) || 5 external CT 0.3 mOhm)
  • Web Services: viewing of captured waveform || web page || pass/fail report for IEEE 519 || pass/fail report for EN 50160 || ITIC (CBEMA) curve || SEMI curve || NEMA motor derating curve || alarm notification by e-mail || TLS 1.2 || push historical data via mail
  • Width: 160 mm
  • Display Type: remote LCD display || colour touchscreen
  • Depth: 135.3 mm
  • Accuracy Class: class 0.1S active energy IEC 62053-22 || class 0.1 active energy IEC 61557-12 || class 0.1 active energy ANSI C12.20 || class 0.5S reactive energy IEC 62053-24 || class 0.1 current IEC 61557-12 || class 0.1 voltage IEC 61557-12 || class 0.1 active power IEC 61557-12 || class 0.5 power factor IEC 61557-12
  • Maximum Power Consumption In Va: 80 VA 480 V AC

Offer Sustainability

  • Rohs Exemption Information: Yes
  • Mercury Free: Yes
  • Environmental Disclosure: ENVPEP1801009EN
  • Sustainable Offer Status: Green Premium product
  • Reach Regulation: Free of Substances of Very High Concern above the threshold
  • California Proposition 65: WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
  • Reach Free Of Svhc: Yes
  • Weee: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
  • China Rohs Regulation: X
  • Circularity Profile: ENVEOLI1801009EN
  • Eu Rohs Directive: Compliant

Environment

  • Ambient Air Temperature For Operation: -25-70 °C
  • Standards: ANSI C12.20 || ANSI C37.90.1 || IEC 61000-4-15 || IEC 61000-4-30 || IEC 61010-1 || IEC 61326-1 || IEC 61557-12 || IEC 61850 || IEC 62052-11 || IEC 62052-31 || IEC 62053-22 || IEC 62053-23 || IEC 62053-24 || IEC 62586 || UL 61010-1
  • Degree Of Protection: UL type 12, front
  • Electromagnetic Compatibility: EMC immunity IEC 62052-11 || EMC immunity IEC 61326-1 || EMC immunity IEC 61000-6-5 || electrostatic discharge immunity test IEC 61000-4-2 || immunity to radiated fields IEC 61000-4-3 || immunity to fast transients IEC 61000-4-4 || surge immunity test IEC 61000-4-5 || immunity to conducted disturbances IEC 61000-4-6 || immunity to magnetic fields at network frequency IEC 61000-4-8 || immunity to conducted disturbances 2...150 kHz CLC/TR 50579 || voltage dips and interruptions immunity test IEC 61000-4-11 || immunity to impulse waves IEC 61000-4-12 || conducted and radiated emissions EN 55011 || conducted and radiated emissionsclass B EN 55032 || conducted and radiated emissionsclass B FCC part 15 || conducted and radiated emissionsclass B ICES-003 || surge withstand ANSI C37.90.1 || surge withstand IEEE C37.90.1
  • Ambient Air Temperature For Storage: -40-85 °C
  • Relative Humidity: 5-95 %
  • Quality Labels: ISO 9001 || ISO 14000
  • Ip Degree Of Protection: front IP65 || rear IP30
  • Operating Altitude: 0...9842.52 ft (0...3000 m)
  • Installation Category: III

نظرات کاربران درباره کنتور هوشمند اشنایدر الکتریک

نظری در مورد این محصول توسط کاربران ارسال نگردیده است.
اولین نفری باشید که در مورد کنتور هوشمند اشنایدر الکتریک نظر می دهد.

ارسال نظر درباره کنتور هوشمند اشنایدر الکتریک

لطفا توجه داشته باشید که ایمیل شما منتشر نخواهد شد.
 
کد امنیتی *
captcha
قیمت: لطفاً تماس بگیرید
کد محصول ION9000 METSEION92040
وضعیت موجودی تعداد 1